Copper Stationary Terminal Flange for Vacuum Circuit Breakers
Video
Short Description
Cymber Metal supplies custom copper stationary terminal flanges for vacuum circuit breaker assemblies. These pure copper components combine a raised mounting face, a central locating recess, threaded mounting holes and a rounded outer flange.
Material, contact interfaces, annular grooves and optional plating are specified to approved drawings. The illustrated four-hole design is a reference configuration; electrical ratings and dielectric performance depend on the complete equipment design and validation.
Key Features
- Raised contact mounting face with drawing-defined locating and fastening features.
- Rounded outer profile and annular clearance groove machined to the required geometry.
- Custom copper grade, hole pattern, surface finish and plating specification.
Manufacturing & Quality Control
| Stage | Scope |
|---|---|
| Material and Drawing Review | Confirm grade, blank route, mating parts, datums and acceptance criteria |
| CNC Machining | Use CNC machining support for faces, recesses, annular grooves and threaded features |
| Finishing | Deburr and clean; apply specified surface treatment or plating with agreed masking |
| Final Inspection | Check critical dimensions, threads and surfaces; complete agreed material/coating tests and protective packaging |
For inspection methods and available documentation, see our Quality Assurance page. Product-specific testing and acceptance criteria are confirmed before order placement.
Typical Applications
- Stationary terminal and conductive flange assemblies in vacuum circuit breakers.
- Contact mounting bases in drawing-defined embedded-pole assemblies.
- Tulip-contact supports and conductive connections in switchgear; GIS applications subject to equipment-specific review.
Copper Stationary Terminal Flange FAQ
It provides a conductive mounting interface in the specified circuit-breaker assembly. The raised face, locating recess and threaded holes connect to the mating contact system. It is not, by itself, an arc-interrupting contact or a hermetic vacuum-sealing flange.
C11000, C10200 and C10100 can be reviewed against the required conductivity, oxygen content, material condition and processing route. State the grade and material standard on the drawing; different national grade designations are not automatically interchangeable.
Requirements are reviewed feature by feature rather than applied as a blanket tolerance. Specify datums, runout, flatness, hole position and roughness, and identify whether dimensions apply before or after plating.
No. The rim and annular groove are drawing-defined geometry, not proof of a voltage rating or partial-discharge performance. Electric-field distribution, insulation clearances and equipment-level dielectric testing must be assessed for the complete assembly.
Full or selective silver plating can be reviewed, with tin or nickel where specified. Provide coating thickness, undercoat, masking and acceptance requirements. Critical fits and contact-face dimensions must account for the coating.
Material certificates, dimensional reports and coating records can be agreed with the order. Conductivity, roughness, thread-gauge and ultrasonic inspection require defined methods and coverage. EN 10204 Type 3.1 documentation should be confirmed before order placement.
Request a Quote
Contact Cymber Metal with your 2D/3D drawing, copper grade, quantity, mating-contact details, critical tolerances, surface/plating requirements, inspection documents, destination and required delivery date. Include equipment voltage class and current requirements for technical review.