Copper T-Shaped Conductor Connector for Switchgear

Short Description:

Item Specification
Product Copper T-Shaped Conductor Connector / Contact Housing Tee
Material Options C11000 (ETP), C10200 (oxygen-free) or C10100 (oxygen-free electronic copper), as specified
Applicable Standards ASTM B152/B152M or ASTM B187/B187M where applicable to plate/bar feedstock; forging specifications agreed for the selected grade and route. Finished component acceptance to the approved drawing
Production Route Forging followed by CNC finishing where suitable; alternative blank routes by technical agreement
Overall Length 60–500 mm indicative range; subject to drawing review
Branch Height 50–400 mm indicative range; measurement datums defined by drawing
Main Body Outer Diameter 30–250 mm indicative range
Internal Bore Diameter 15–200 mm indicative range; wall thickness and groove geometry subject to review
Contact and Mounting Features Stepped bores, internal contact grooves, machined end faces, mounting holes and threads to drawing
Tolerance Bore fits, coaxiality, face orientation and surface roughness according to the approved drawing and process review
Surface Finish Machined functional surfaces; external texture, cleaning and anti-tarnish treatment as specified
Plating Options Optional full or selective silver, tin or nickel plating; coverage, thickness and acceptance criteria agreed before production
Inspection Material verification, bore/groove dimensions, alignment, mounting faces, threads and surface condition; conductivity, internal-soundness and coating tests as agreed
Documentation MTC, dimensional reports and coating records as specified; EN 10204 Type 3.1 documentation subject to order confirmation

Product Detail

Product Tags

Video

Short Description

Cymber Metal supplies custom copper T-shaped conductor connectors for switchgear, circuit-breaker and GIS assemblies. Made from specified pure copper, the T-shaped body combines machined conductor bores with a branch mounting interface.

Internal grooves, bore fits, mounting holes and optional plating are prepared to approved drawings. Contact interfaces are matched to the specified mating conductor and contact system; electrical ratings depend on the complete equipment design and validation.

Key Features

  • T-shaped geometry for drawing-defined conductor branching and contact support.
  • Machined bores and internal grooves matched to the selected contact system.
  • Branch mounting face with custom hole positions and thread requirements.
  • Copper grade, surface treatment and inspection scope selected to the application specification.

Manufacturing & Quality Control

Stage Scope
Technical Review Confirm copper grade, blank route, mating conductors, contact-system data, datums and inspection requirements
Forming and Machining Select the blank route and use CNC machining support for bores, grooves, mounting faces and threaded features
Finishing Deburr bore intersections and edges; clean and apply optional surface treatment or plating to specification
Inspection Verify drawing-defined features and agreed material/coating requirements before protective packaging

For inspection methods and available documentation, see our Quality Assurance page. Product-specific testing and acceptance criteria are confirmed before order placement.

Typical Applications

  • Vacuum circuit-breaker outgoing conductor assemblies.
  • GIS main-circuit conductor branches.
  • Switchgear busbar connections and contact housings.
  • Transformer and industrial high-current transition nodes.

Equipment voltage class, continuous current, short-circuit duty and dielectric performance require assembly-level design validation.

Copper T-Shaped Conductor Connector FAQ

What is this copper T-shaped connector used for?

It forms a conductive branch or contact-support interface in a drawing-defined electrical assembly. Unlike a plumbing tee, its functional requirements concern conductor fit, electrical contact, mounting geometry and equipment validation rather than fluid service.

Which copper grades can be specified?

C11000, C10200 and C10100 can be reviewed against the required material standard, condition and operating requirements. Specify conductivity or oxygen-content requirements separately; grades from different national standards should not be treated as automatically equivalent.

Is the connector forged or machined from solid stock?

The route depends on geometry, material and quantity. A near-net forged blank may reduce material removal, while another approved stock or forming route may suit a different order. The selected route and inspection requirements are confirmed before production.

Can the internal grooves fit contact bands or finger contacts?

Grooves can be reviewed for the specified contact system. Supply the contact manufacturer’s installation dimensions, mating-conductor size and required surface finish. Groove appearance alone does not establish compatibility with a particular contact brand or model.

Can you provide H7 bores or ±0.02 mm tolerances?

These requirements can be reviewed for selected features. H7 is a diameter-dependent tolerance zone, not a universal ±0.02 mm tolerance. Specify nominal dimensions, datums, coaxiality and whether acceptance applies before or after plating.

Is the connector suitable for a particular switchgear voltage class?

Suitability cannot be confirmed from copper grade or external radii alone. Voltage class, clearances, field distribution, contact design and short-circuit duty must be assessed within the complete equipment design. Radiused edges alone do not establish corona-free performance.

Can the bores and contact surfaces be silver-plated?

Full or selective silver plating can be reviewed, with tin or nickel options where specified. Provide coating thickness, undercoat, masked areas and acceptance criteria. Bore and groove dimensions must account for the coating; ASTM B700 may be specified for silver where applicable.

What inspection documents are available?

Material certificates, bore/groove dimensional reports, thread-inspection records and plating reports can be agreed with the order. Conductivity testing, ultrasonic examination or other internal-soundness checks and third-party inspection require defined methods, coverage and acceptance criteria.

Request a Quote

Contact Cymber Metal with your 2D/3D drawing, copper grade and condition, quantity, bore and groove dimensions, contact-system details, tolerances, plating requirements, inspection documents, destination and required delivery date. Include equipment voltage class, current and short-circuit duty where relevant.


  • Previous:
  • Next:

  • Write your message here and send it to us