L-Shaped Copper Busbar Connector with Hexagonal Fastener Recess

Short Description:

Item Specification
Product Custom L-shaped copper busbar connector with hexagonal fastener recess
Geometry Right-angle conductive connector with radiused transition and drawing-specific holes
Primary Material Options C11000 ETP copper; C10200 oxygen-free copper; C10100 oxygen-free electronic copper
Other Material Options C10400/C10700 silver-bearing copper or C18150 CuCrZr, subject to separate electrical and mechanical review
Starting-Material Standards ASTM B187/B187M for applicable bar stock or ASTM B152/B152M for applicable sheet/strip stock; selected according to the production route
Individual Leg Length Indicative range: 15–180 mm
Width Indicative range: 10–120 mm
Thickness Indicative range: 2.5–20.0 mm
Hexagonal Recess Bolt-head or nut seat for nominated M4–M20 hardware, subject to available width, thickness and edge distance
Hole Options Clearance holes, locating holes and drawing-specific fastening features
Pocket Across-Flats Proposed clearance allowance: +0.05 to +0.15 mm relative to the agreed reference dimension; final fit checked with actual hardware
Included Angle Proposed target: 90° ±0.3°, where specified
Contact-Face Flatness Proposed selected-face target: ≤0.03 mm
Contact-Face Roughness Proposed selected-face target: Ra 0.4–0.8 μm
Conductivity A target of ≥98% IACS may be specified for suitable pure-copper grades and conditions, with an agreed test method
Hardness An 85–120 HV target may be reviewed against grade, temper, forming requirements and fastener loading
Surface Finish Bare copper, compatible anti-tarnish treatment, or specified tin, silver or nickel plating
Acceptance Requirements Approved drawing, material specification, finish requirements and agreed inspection plan

Product Detail

Product Tags

Video

Short Description

Cymber Metal supplies custom L-shaped copper busbar connectors with a hexagonal fastener recess for compact bolted electrical connections. The right-angle geometry connects perpendicular interfaces, while the recessed hex seat can restrain a matching bolt head or nut against rotation when correctly dimensioned. Material options include C11000 ETP copper, C10200 oxygen-free copper and C10100 oxygen-free electronic copper. Leg dimensions, hole patterns, pocket geometry and surface finishes are specified to the customer drawing. Potential applications include switchgear terminals, contactor connections, battery distribution units and energy-storage equipment.

L-Shaped Copper Busbar Connector Overview

An L-shaped copper busbar connector is a conductive component that joins electrical interfaces arranged at approximately 90 degrees. This version incorporates a hexagonal recess around one connection hole, providing a shaped seat for a compatible hex bolt head or nut.

The photographed component has two holes on the longer leg, a separate hole on the perpendicular leg, rounded external corners and a radiused transition between the two legs. The hexagonal recess is visible on the reverse face of the larger connection hole.

A correctly matched recess can reduce the need to hold the seated fastener with a second tool during tightening. Its effectiveness depends on pocket depth, across-flats dimensions, corner geometry, copper condition, coating thickness and assembly torque. The recess does not, by itself, retain the fastener axially.

Material selection starts with the required conductivity, forming condition and joint design. Explore our pure copper materials for the broader product range, or review C10200 oxygen-free copper when an oxygen-free grade is specified.

Key Features

Feature Practical Value
Hexagonal Fastener Recess Provides a shaped seat intended to limit rotation of compatible hex hardware during tightening
Right-Angle Connection Links perpendicular conductive interfaces in space-constrained assemblies
Recessed Fastener Seating Can reduce fastener projection when pocket depth and hardware geometry permit
Drawing-Specific Hole Pattern Matches busbar interfaces, mounting positions and required fastener sizes
Radiused Transition Provides a controlled change in direction; bend radius is selected for the material and assembly
Rounded Edges and Corners Reduces sharp-edge handling risks and supports consistent finishing
High-Conductivity Material Options Allows selection of suitable ETP or oxygen-free copper according to the electrical specification
Optional Plating Enables the contact finish to be matched to mating materials and service conditions

A hexagonal recess does not automatically increase electrical clearance or creepage distance. These distances must be checked on the complete assembly, including installed hardware.

Manufacturing & Quality Control

The manufacturing route and inspection plan are selected according to part geometry, material condition, order quantity and fastening requirements.

Manufacturing Process

Stage Process and Control Focus
Drawing and Hardware Review Confirm leg dimensions, contact areas, bend radius, hole pattern, hex fastener dimensions and installation access
Material Selection Select the copper grade, temper and stock form against conductivity, forming and mechanical requirements
Blank Preparation Cut and prepare suitable copper bar or strip; rounded-edge stock may be considered where appropriate
Right-Angle Forming Control tooling, bend radius and material condition to achieve the specified angle and limit surface damage
Hexagonal Recess Production Review precision coining or machining according to pocket depth, corner geometry, quantity and required fit
Hole Machining Produce connection and locating holes with reference to the agreed datums and pocket position
Deburring and Contact-Face Finishing Remove machining burrs and finish designated contact faces without altering critical dimensions
Optional Surface Treatment Apply the specified coating after the appropriate forming and machining stages; allow for coating build-up in the pocket
Final Protection and Packing Protect contact surfaces and separate parts to reduce scratching during handling and transport

Drawing-specific recesses, holes and contact faces can be reviewed through our custom machining services. Available finishing routes are introduced on our busbar plating page.

Quality Control and Inspection

Inspection Item Method and Acceptance Basis
Material Identity Review material documents and use grade-appropriate analytical verification where required
Oxygen-Free Grade Requirements Confirm oxygen-related requirements through suitable certificates or dedicated testing; routine composition screening alone is insufficient
Electrical Conductivity Test using an agreed method with suitable calibration, part geometry and temperature control
Hardness Perform Vickers hardness testing when specified, using an agreed test location and load
Overall Dimensions Check leg lengths, width, thickness, hole diameters and hole locations against the drawing
Hexagonal Recess Geometry Inspect across-flats, depth, corner radii and remaining material thickness using suitable measuring equipment and gauges
Fastener Fit Check actual nominated hardware, including relevant dimensional and coating tolerances
Anti-Rotation Performance Conduct an agreed torque test where required; acceptance covers pocket deformation, fastener rotation and visible damage
Angle and Contact Faces Inspect included angle, selected-face flatness and surface roughness where specified
Surface and Bend Condition Inspect edges, transition regions and contact surfaces for unacceptable burrs, cracks or damage
Plating Verify specified coating thickness, coverage and other order-specific acceptance requirements
Documentation and Traceability Agree material records, batch identification, dimensional reports and any third-party inspection before production

Inspection scope and sampling frequency are defined in the order requirements. EN 10204 3.1 documentation, where required and applicable, must be agreed before ordering.

See our quality assurance procedures for further information on inspection and quality management.

Typical Applications

These are potential integration applications, subject to the equipment manufacturer's design review and validation.

Application Typical Use Design Considerations
Molded-Case Circuit Breakers Compact inlet or outlet terminal connections Pocket strength, terminal temperature rise, fastener access and enclosure clearances
Air Circuit Breakers and Disconnectors Right-angle connections between terminal pads and busbars Short-circuit loading, joint pressure, conductor section and mechanical support
EV Battery Distribution Units Bolted connections between internal busbars and electrical devices Vibration, insulation coordination, thermal cycling and assembly sequence
High-Voltage DC Contactors Connection adapters between contactor studs and busbar interfaces Stud loading, installation torque, contact finish and system voltage
Energy-Storage PCS Equipment Conductive links within power-conversion assemblies Operating current, ventilation, temperature rise and service access
Industrial Control Cabinets Custom right-angle power-distribution connections Hole alignment, mating surfaces, fastening method and available installation space

Frequently Asked Questions

What is an L-shaped copper busbar connector?

It is a copper conductive component that joins interfaces positioned at approximately 90 degrees. This version includes a hexagonal fastener recess around one hole to accommodate compatible hex hardware. It is a bolted connection component, not a cable-crimp lug.

What does the hexagonal recess do?

The recess provides a shaped seat that can restrain a matching bolt head or nut against rotation. Its performance depends on pocket dimensions, engagement depth, material condition and tightening torque. Axial fastener retention requires a separate feature or assembly arrangement.

Does it allow single-tool assembly?

It can, when the seated hardware is adequately restrained and the opposite side is accessible for tightening. Single-tool installation must be verified with the actual fastener, pocket geometry and assembly procedure. The recess alone does not guarantee wrench-free installation in every configuration.

Which copper grade should be selected?

C11000 is ETP copper, while C10200 and C10100 are oxygen-free grades with different specification requirements. Selection depends on conductivity, processing, service conditions and documentation needs. Material grades from different standards should not be treated as automatically interchangeable.

Can the recess fit either a bolt head or a nut?

Yes, the design can be specified for either, but the dimensions must match the selected hardware. Bolt heads and nuts can differ in height, chamfer and tolerances. Provide the fastener standard, size and drawing before finalizing pocket dimensions.

Can the connector be tin-, silver- or nickel-plated?

These finishes can be reviewed according to the application. Specify coating type, thickness, contact areas and any masking requirements. Coating build-up must be included in the pocket-fit review, particularly where fastener clearance is small.

What current or voltage can this connector handle?

There is no single rating based on shape alone. Current capacity depends on conductor section, contact resistance, cooling and allowable temperature rise. Voltage suitability also depends on the complete insulation system, installed hardware, clearance, creepage and applicable equipment standards.

What information is needed for a quotation?

Send the drawing, copper grade and temper, quantity, leg dimensions, hole pattern, pocket dimensions, actual fastener details and surface finish. Include critical tolerances, torque requirements, operating conditions, inspection documents, destination and requested delivery schedule.

Request a Quote

Required Information Details to Provide
Drawing Dimensioned 2D drawing and, where available, a 3D model
Material Copper grade, material standard, temper and any conductivity or hardness requirement
Geometry Leg lengths, width, thickness, bend radius and included angle
Connection Features Hole sizes, hole pitch, datums and required contact areas
Hexagonal Recess Across-flats, depth, corner requirements and remaining wall thickness
Fastener Bolt or nut standard, size, dimensional drawing and intended tightening torque
Surface Finish Bare copper or coating type, thickness, masking and contact-face requirements
Quantity Prototype quantity, batch quantity and estimated annual usage
Operating Conditions Current, voltage, temperature, vibration and installation environment
Inspection and Documents Dimensional report, material documentation, functional testing and third-party inspection requirements
Delivery Destination country, packaging requirements and requested schedule

Contact Cymber Metal for a drawing-based quotation for your custom L-shaped copper busbar connector.


  • Previous:
  • Next:

  • Write your message here and send it to us